Forcing Analog Outputs - Eaton EMR-3MP0 Installation, Operation And Maintenance Manual

Motor relay
Table of Contents

Advertisement

8.3.5

Forcing Analog Outputs*

* = Availability depends on ordered device.
The parameters, their defaults, and setting ranges have to be taken from Analog Output
section.
Principle – General Use
The User MUST ENSURE that the Analog Outputs operate normally after maintenance is
completed. Do not use this mode if forced Analog Outputs cause issues in external
processes.
For commissioning purposes or for maintenance, Analog Outputs can be set by force.
Within this mode [Service / Test Mode (Prot inhibit) / WARNING! Cont? / Analog Outputs],
Analog Outputs can be set by force:
• Permanent; or
• Via timeout.
If they are set with a timeout, they will keep their "Forced Value" only as long as this
timer runs. If the timer expires, the Analog Output will operate normally. If they are set
as »Permanent«, they will keep the "Forced Value" continuously. This menu will show the
current value that is assigned to the Analog Output until the User activates the force
mode by calling up the »Function«. As soon as the force mode is activated, the shown
values will be frozen as long as this mode is active. Now the User can force Analog Output
values. As soon as the force mode is deactivated, measured values will again be shown.
EMR-3MP0
NOTICE!
DANGER!
www.eaton.com
8 Commissioning
8.3 Service and Commissioning Support
231