7 Self-Supervision
Self-Supervision within the devices
Supervision of...
Device Start (Reboot)
The device starts up if:
• it is connected to the supply voltage,
• the user initiates (intentionally) a restart of the device,
• the device is set back to factory defaults,
• the internal self-supervision of the device detects a fatal error.
The reason for a device start/reboot is shown numerically within menu [Operation / Status
Display / Sys] »Reboot« (please refer to the table below). The reason will also be logged
within the event recorder (Event: »Sys . Reboot«).
The table below explains the numbers indicating the reason of the restart.
Device Start-up Codes
1.
Normal Start-up
Start-up after clean disconnection of the supply voltage.
2.
Reboot by the Operator
Device reboot triggered by the operator via HMI or PowerPort-E.
3.
Reboot by means of Super Reset
Automatic reboot when setting the device back to factory defaults.
4.
-- (outdated)
5.
-- (outdated)
6.
Unknown Error Source
Reboot due to unknown error source.
220
Supervised by...
www.eaton.com
Action on detected issue...
[Operation / Status Display /
SCADA].