Phase and Ground Current Inputs:
Nominal Currents:
Max. Measuring Range:
Load Capacity:
Overcurrent Proof:
Power Consumption:
Current and Ground Current Measurement (Card "TI‑MP")
Fig. 58: MP‑3000-compatible current measurement input card.
EMR-3MP0
1 A / 5 A
Up to 40 x In (phase currents)
Up to 25 x In (ground current standard)
4 x In / continuously
30 x In / 10 s
100 x In / 1 s
250 x In / 10 ms (1 half-wave)
Phase current inputs
At In = 1 A: S = 25 mVA
At In = 5 A: S = 90 mVA
Ground current input
At In = 1 A: S = 25 mVA
At In = 5 A: S = 90 mVA
1.00 Nm
9.0 lb⋅in