10 Technical Data EMR-3MP0
Voltage Supply
Aux. Voltage:
Buffer Time in Case of Supply Failure:
Max. Permissible Making Current:
Fuse (built into the wide-range power supply
unit):
The voltage supply must be protected by a fuse of:
• 2.5 A time-lag miniature fuse 5 x 20 mm (approx. 1/5 x 0.8 in.) according to IEC
60127
• 3.5 A time-lag miniature fuse 6.3 x 32 mm (approx. 1/4 x 1 ¼ in.) according to UL
248-14
Power Consumption
Power Supply Range
24 – 270 Vdc:
48 – 230 Vac (for Frequencies of
50-60 Hz):
Display
Display type:
Resolution - graphics display:
LEDs
LED type:
Number of LEDs, Housing B1:
Front Interface USB
Type:
240
24 - 270 Vdc / 48 - 230 Vac (−20/+10%) ≂
≥ 50 ms at minimal aux. voltage
Interrupted communication is permitted.
18 A peak value for ≤0.25 ms
12 A peak value for ≤1 ms
6.3 A time-lag
(This fuse is not to be replaced by the user, but
is necessary for safe operation.)
Power consumption in Idle
Mode
Approx. 7 W
Approx. 7 W / 13 VA
LCD with LED background illumination
128 x 64 pixel
Two colored: red / green
8
Mini B
www.eaton.com
Max. Power Consumption
Approx. 10 W
Approx. 10 W / 17 VA