5 Recorders

5.7 History Function

5.7
History Function
The History function, accessible under the menu branch [Operation / History], can be
utilized as a counter or log of specific occurrences monitored by the device.
There are the following groups, each dedicated to a particular type of occurrence that can
be recorded:
• Operations [OperationsCr];
• Pickups [PickupCr];
• Trips [TripCr];
• Totals [TotalCr].
To View the History Records at the HMI
• Enter the menu [Operation / History].
• Scroll down by means of the Softkey "▼" within this list up to that group you want to
change in. Enter this sub-menu by pressing the Softkey "▶".
• Scroll down by means of the Softkey "▼" within this list up to that counter/entry that
you want to take a look at. View details of this counter by means of pressing the
Softkey "▶".
To View the History Records with PowerPort-E
As a general preparation, start PowerPort-E and synchronize the device data by
clicking »Receive Data From The Device« in the menu »Device«.
• Enter the EMR-3MP0 menu [Operation / History].
• Double click onto that group of counters you want to view.
• A window opens with all counter details (for the selected group) in tabular form.
To Reset the History Records at the HMI or with PowerPort-E
• Enter the EMR-3MP0 menu [Operation / Reset / History].
• There are the following Direct Commands available in this menu branch:
◦ »Res OperationsCr« — Reset all Operation counters;
◦ »Res AlarmCr« — Reset all Pickup counters;
◦ »Res TripCr« — Reset all Trip counters;
◦ »Res TotalCr« — Reset all "Totals" counters;
◦ »Res All« — Reset all History counters, irrespective of their group;
• In order to reset the group of counters, execute the respective Direct Command. You
might be asked to enter your password.