• When changing the substation configuration, usually a new *.SCD file has to be
generated. This *.SCD file must be transmitted to all devices by means of PowerPort-
E. If the file is not transmitted to all devices, IEC 61850 malfunctions will be the
result.
• If changing the device planning after the completion of the substation configuration,
changes in the corresponding *.ICD file may result. This, in turn, may make an
update of the *.SCD file necessary.
IEC 61850 Virtual Outputs
In addition to the standardized logical node status information, up to 32 free configurable
status information items can be assigned to the 32 Virtual Outputs. This can be done in
the [Device Para / IEC 61850] menu.
IEC 61850 – Virtual Inputs
If there is an INPUT defined in the SCD file the status of the input can be checked at
[Operation / Status Display / IEC 61850 / VirtualInput] »VirtInpx«. For every status bit
there is a corresponding Quality bit at [Operation / Status Display / IEC 61850 /
VirtualInput] »Quality of GGIO Inx«.
GOOSE Status
The status of the GOOSE connection can be checked at [Operation / Status Display / IEC
61850 / State] »All Goose Subscriber active«. This signal summarizes the Quality of all
Virtual Inputs (see above).
EMR-3MP0
WARNING!
www.eaton.com
3 Communication Protocols
3.5 IEC 61850
121