Eaton EMR-3MP0 Installation, Operation And Maintenance Manual page 221

Motor relay
Table of Contents

Advertisement

Device Start-up Codes
7.
Forced Reboot (initiated by the main processor)
The main processor identified invalid conditions or data.
8.
Exceeded Time Limit of the Protection Cycle
Unexpected interruption of the Protection Cycle.
9.
Forced Reboot (initiated by the digital signal processor)
The digital signal processor identified invalid conditions or data.
10.
Exceeded Time Limit of the Measured Value Processing
Unexpected interruption of the cyclic measured value processing.
11.
Sags of the Supply Voltage
Reboot after short-term sag or outage of the supply voltage.
12.
Illegal Memory Access
Reboot after illegal memory access.
Internal Messages
The menu [Operation / Self-Supervision / Messages] gives access to the list of internal
messages. In particular, it is recommended to check these in case of some problem
directly related to the functionality of the EMR-3MP0.
All messages that can potentially appear here are described in detail in a separate
document, the "E‑Series Troubleshooting Guide" (MN026003EN).
Device Taken out of Service ("Device Stopped")
The protection device will be taken out of service, if there is an undefined state that
cannot be escaped after three reboots.
In this state the system LED will be illuminated red or red flashing. The display will show
the message "Device Stopped" followed by a 6-digit error code, e.g. E01487.
In addition to the recorders, messages and display information that can be accessed by
the user, there may exist additional error information accessible by the Service Staff.
These offer further failure analysis and diagnosis opportunities to the Service Staff.
EMR-3MP0
www.eaton.com
7 Self-Supervision
221

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents