Eaton EMR-3MP0 Installation, Operation And Maintenance Manual page 242

Motor relay
Table of Contents

Advertisement

10 Technical Data EMR-3MP0
Un = 110 / 120 Vac / dc
Switching Threshold 3 ON:
Switching Threshold 3 OFF:
Un = 230 / 240 Vac / dc
Switching Threshold 4 ON:
Switching Threshold 4 OFF:
Terminals:
Relay Outputs
Continuous current:
Max. make current:
Max. breaking current:
Max. switching voltage:
Switching capacity:
Operating time: (*)
Reset time: (*)
Contact type:
Terminals:
(*) The operating and reset times are the pure hardware-related switching times (coil –
making/breaking contact), i. e. without the time that it takes the software to calculate the
decisions.
242
Min. 88.0 Vdc / 88.0 Vac
Max. 44.0 Vdc / 44.0 Vac
Min. 184 Vdc / 184 Vac
Max. 92 Vdc / 92 Vac
Screw-type terminal
5 A ac / dc
25 A ac / dc for 4 s
1000 W (VA) at L/R = 40 ms
30 A / 230 Vac according to ANSI IEEE Std
C37.90-2005
30 A / 250 Vdc according to ANSI IEEE Std
C37.90-2005
5 A ac up to 240 Vac
4 A ac at 230 V and cos φ = 0,4
5 A dc up to 30 V (resistive)
0.3 A dc at 250 V (resistive)
0.1 A dc at 220 V and L/R = 40 ms
250 Vac / 250 Vdc
3000 VA
typ. 7 ms
typ. 3 ms
1 changeover contact or normally open or
normally closed
Screw-type terminals
www.eaton.com
EMR-3MP0