Electrical Data - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

System description
3
Technical data

3.4.2 Electrical data

22 | 124
Building Technologies
Fire safety
Rating detector line
Operating voltage
Operating current
Line resistance / capacitance
Monitored for earth fault
Monitored for open / short circuit
Sounders on mainboard
Voltage / current
EOL element
AUX. power output (max.)
Configurable IOs on mainboard
Voltage / current
Outputs on output card (4M) FCA3602-Z1
Voltage / current
EOL element
Additionally for outputs on output card (4M) FCA3602-Z1 with the functionality
'creeping open / creeping short'
Line resistance
Sounder voltage
Relay outputs on mainboard
Power supply
Mains voltage
Mains fuse
Power consumption
Max. nominal output current with battery
charging, I
max a
Max. nominal output current without battery
charging, I
max b
Min. output current
System supply voltage
Mains failure delay
Battery low discharge cut off
Temperature compensation
DC 12...33 V
Max. 0.5 A
Max. 240 Ω / Max. 500 nF
Yes
Yes
DC 24 V / 0.5 A
1
Resistor 2.2 kΩ / 1 W / 0.5 %
DC 24 V / 0.2 A
DC 24 V / 0.1 A
2
DC 26 V / 1.0 A
3
Resistor 2.2 kΩ / 1 W / 0.5 %
Max. 74.3 Ω
Min. DC 16 V
DC 60 V / 2.0 A
AC 97...127 V
AC 196...253 V
AC 250 V / 2.5 AT
70 W
0.9 A
2.5 A
0.05 A
DC 20.5...28.6 V
1 min., 5 min., 10 min., 29 min.
DC 20.5...21 V
Yes
A6V10421795_en--_g
2016-11-18

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc361-zzFc361-zaFc361-yzFc361-ya

Table of Contents