Led Indicators - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Function overview
6

LED indicators

6.2 LED indicators
No.
Description
1
Alarm
2
More alarm
3
Fire brigade
4
System on
5
Alarm delay off
6
Manned /
Unmanned
7
General fault
8
System fault
9
Sounder fault
10
RT fire fault
11
Test condition
12
Isolation
13
Silence
14
Resound
15
Reset
16
Acknowledge
56 | 124
Building Technologies
Fire safety
FC360
1
2
3
4
5
6
7
8
9
Color
Status
Function
Red
On
The panel is in 'Alarm' condition.
Red
Flashing More than two alarm events happen.
Red
On
Depends on the configuration:
Option 1: Fire brigade was called.
Option 2: RT fire output relay is activated. Call the fire brigade.
Green
On
The panel is in operation.
Yellow
Flashing The panel is in investigation time (T2) of AVC process.
Yellow
On
The panel is in 'Manned' operation.
Off
The panel is in 'Unmanned' operation.
Yellow
On
Indicate any fault event in the system.
Yellow
On
Indicate CPU failure.
Yellow
On
All sounder devices are disabled.
Flashing One or more sounders are in fault.
Yellow
On
All RT fire devices are disabled.
Flashing One or more RT fire devices are in fault.
Yellow
On
Indicate one or more zones are in test mode.
Yellow
On
Indicate there are isolation events.
Red
On
All sounder devices are silenced.
Red
On
All sounder devices are activated.
Yellow
Flashing There are acknowledged alarm events which are waiting for
reset.
Yellow
Flashing There are alarm / fault events need to be acknowledged.
10
11
12
13 14
15 16
A6V10421795_en--_g
2016-11-18

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc361-zzFc361-zaFc361-yzFc361-ya

Table of Contents