Operation
7
Alarm procedure in unmanned mode
7 Operation
7.1 Alarm procedure in unmanned mode
64 | 124
Building Technologies
Fire safety
This chapter describes detailed operation workflow on important fire detection
system functions.
●
Display provides fire information. See chapter 'Event views [➙ 62]'.
●
Immediate activation of panel states 'Any Fire' and 'Global Alarm'.
●
If configured: RT fire is activated by 'Global Alarm'.
Examine the fire location and decide whether it is a MAJOR INCIDENT or MINOR
INCIDENT.
MAJOR INCIDENT: A real fire emergency
Press <Acknowledge>
attendance.
(Access level 2 password is required.)
→ Buzzer is off.
Optional: Press <Silence/Resound>
silence/resound all sounders.
Read the alarm event information on the LCD and
go to the indicated fire location to verify the incident.
Ensure the fire brigade is called.
Call fire brigade if no remote transmission is
implemented!
If remote transmission to fire brigade is
implemented, the 'Fire Brigade' LED
'RT fire' status. See chapter LED indicators [➙ 56].
to confirm
to
indicates
A6V10421795_en--_g
2016-11-18