Siemens FC361 Series Technical Manual page 75

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

7.5.2.2 Lamp test
Building Technologies
Fire safety
The lamp test checks the following functions:
LEDs
Buzzer
LCD
1. Press
on the keypad, the 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
7 - Logout
8 - Query alarm counter
2. Select 'Operation' and press
Operation
1 - Isolation
2 - Test
3. Select 'Test' and press
Test
1 - Detection test
2 - Lamp test
4. Select 'Lamp test ' and press
Do you want to activate
lamp test?
Yes (OK) or No (C)
5. Press
to confirm, test starts:
LEDs: on 10 s
Buzzer: on 10 s
LCD: on 5 s, then off
The panel returns to the previous status after finishing check.
L2
, the 'Operation' window is open.
L2
, the 'Test' window is open.
L2
, a confirmation dialog window is open.
Operation
7
Access level 2
75 | 124
A6V10421795_en--_g
2016-11-18