8.4.5 Auto configuration

Building Technologies
Fire safety
The 'Auto configuration' function is used to commission a newly installed panel
immediately.
NOTICE
Overwrite the old configuration
The old configuration is overwritten.
Save the old configuration before executing auto configuration.
w The detector line is powered off. Refer to chapter 'Power off [➙ 84]'.
1. Press
on the keypad.
a The 'Main menu' window is open.
2. Select 'Engineering' and press
a The 'Engineering' window is open.
3. Select 'Detector line' and press
a The 'Detector line' window is open.
4. Select 'Auto configuration' and press
a A warning window is open.
5. Press
to confirm.
a The detector line starts auto configuration.
a The detector line restarts and all connected devices are found and added to the
detector line according to the topology.
a Set all the devices to the default settings. (see 'Appendix D: Default setting for
panel/devices [➙ 117]')
a The devices are assigned to the corresponding zones automatically. (see
'Appendix B: Zone type list [➙ 115]')
a Auto restart the panel for the configuration to take effect.
a All the devices can be viewed on the PMI. (see chapter 'Locate devices
[➙ 91]')
The 'Auto configuration' process takes a few minutes, depending on the
installation size.
A FDCI723 zone module connected to the system is not automatically assigned to
a zone after auto configuration. The fault 'Unassigned zone' is reported. It must
be assigned to a zone manually by 'FC360 Panel Configurator'.
If the auto configuration process is terminated by fault the old configuration is
recovered on the panel!
.
.
.