Reset Alarm Counter; Restore Factory Settings - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Engineering
8

Reset alarm counter

8.6 Reset alarm counter

8.7 Restore factory settings

94 | 124
Building Technologies
Fire safety
The 'Alarm counter reset' function is used to reset the alarm counter to '0'.
1. Press
on the keypad.
a The 'Main menu' window is open.
2. Select 'Engineering' and press
a The 'Engineering' window is open.
3. Select 'Alarm counter reset' and press
a A password entry window is open.
4. Enter the password (66666666) and press
a A confirmation dialog window is open.
5. Press
to confirm.
a The alarm counter is reset to '0'.
NOTICE
Restoring factory settings on the panel
The configuration of the panel is deleted!
Save the configuration data for the panel before restoring to factory settings.
The restore process takes a few minutes, depending on the size of site.
1. Press
on the keypad.
a The 'Main menu' window is open.
2. Select 'Engineering' and press
a The 'Engineering' window is open.
3. Select 'Factory set' and press
a A confirmation dialog window is open.
4. Press
to confirm.
a A message 'Factory set is ongoing...' is displayed.
a The panel restarts.
5. Select country and language.
a The panel is reset to factory settings.
.
.
.
.
.