8.4.4.2 Accept replaced devices
Building Technologies
Fire safety
If several devices of the detector line need to be replaced, power off the line first
and then uninstall the old devices. Replace the new devices with the same type
and then operate on PMI as per the procedure below. The new devices inherit all
features and parameters settings from the old devices.
Do not change the topology when replacing devices.
w The detector line is powered off. Refer to chapter 'Power off [➙ 84]'.
1. Press
on the keypad.
a The 'Main menu' window is open.
2. Select 'Engineering' and press
a The 'Engineering' window is open.
3. Select 'Detector line' and press
a The 'Detector line' window is open.
4. Select 'Maintenance' and press
a The 'Maintenance' window is open.
5. Select 'Accept replaced devices' and press
a A list of all lines is displayed.
6. Select a line and press
a A confirmation dialog window is open.
7. Press
to confirm.
a The replaced devices are accepted.
.
.
.
.
.