Operation
7
Access level 2
74 | 124
Building Technologies
Fire safety
4. Select 'Detection test' and press
Test - Detection test
1 - Silent
2 - Audible
5. Select one item, e.g. 'Silent' and press
Detection test - Silent
01 Section 1(OFF)
02 Section 2(OFF)
T1 Section T1(OFF)
6. Select the desired section and press
under the section are displayed.
Detection test - Silent
Entire section (OFF)
001 Auto alarm zone 1(OFF)
002 Auto alarm zone 2(OFF)
003 Auto alarm zone 3(OFF)
7. Select e.g. 'Entire section' and press
Do you want to activate
test on section?
Yes (OK) or No (C)
8. Press
to confirm, the selected section is set to 'Test' mode and the 'Test'
LED is on.
9. You can start testing devices installed in the section.
Refer to the steps above to exit test mode after finishing testing.
, the 'Detection test' window is open.
L2
, a list of all sections is displayed.
L2
, 'Entire section' and a list of all zones
L2
, a confirmation dialog window is open.
A6V10421795_en--_g
2016-11-18