6.3 Keys
No.
Description
1
More Alarm
2
Manned / Unmanned
3
Alarm Delay Off
1
4
Silence
1
Resound
1
5
Reset
1
6
Acknowledge
1
7
Silence buzzer
8
Cancel
9
Ok
10
Keypad
11
Menu
12
Navigation
Building Technologies
Fire safety
FC360
1
2
3
Function
Moves to the next 'fire alarm' event when the 'More Alarm' LED is flashing.
Switches between 'Manned' / 'Unmanned'.
1
Stops the 'Alarm delay time'. The panel generates directly a global alarm.
Silences the sounders in the event of alarm.
●
Manually re-activate the sounders during alarming.
●
If configured, activation of all sounders.
Resets the acknowledged events.
●
Acknowledges all unacknowledged events (alarm and faults) in system.
●
Starts the investigation time T2 (AVC).
●
Silences the buzzer until a new alarm event occurs.
●
Silences the sounder until a new event occurs (if programmed).
Silences the buzzer until a new event (alarm or fault) occurs.
●
In view mode: Returns to upper level.
●
In input / edit mode: Cancels input and return to previous context.
●
In view mode: Jumps to selected sub menu or confirm the selection.
●
In input / edit mode: Confirms the input and returns to upper level.
●
In view mode: Directly jumps to the selected sub menu.
●
In input / edit mode: Enters digits / letters.
Displays the main menu.
▲: Scrolls up.
▼: Scrolls down.
◄: In view mode: Returns to upper level;
In input / edit mode: Deletes last input;
Edit time: Selects previous value.
►: In view mode: Jumps to sub menu.
In input / edit mode: Confirms the input and returns to upper level.
Only available in access level 2 and access level 3
1
Function overview
12
11
10
4
5
6
7
8
9
A6V10421795_en--_g
6
Keys
57 | 124