Engineering
8
Detector line
8.4.4.3 Replace and test a detector
88 | 124
Building Technologies
Fire safety
If a detector needs to be replaced with the same type, set the detector to replace
mode on the PMI as per the procedure below.
1. Press
on the keypad.
a The 'Main menu' window is open.
2. Select 'Engineering' and press
a The 'Engineering' window is open.
3. Select 'Detector line' and press
a The 'Detector line' window is open.
4. Select 'Maintenance' and press
a The 'Maintenance' window is open.
5. Select 'Replace & test detector' and press
a A list of all lines is displayed.
6. Select a line and press
a A list of all detectors is displayed.
7. Select a detector and press
a A confirmation dialog window is open.
8. Press
to confirm.
a The detector is in replace mode. The LED on the old detector is flashing.
a The panel reports an information event and two disable events: the
detector is disabled and the zone which the detector is assigned to is also
disabled. You cannot enable the detector and the zone manually before the
detector exits the replace mode.
9. Uninstall the old detector and wait for approximately 20 s, then insert a new
one with the same type.
a The LED on the new detector flashes for 10 s.
10. After the LED stops flashing, exit the replace mode. Refer to step 1...8.
a The information event and disable events disappear automatically.
The detector exits replace mode automatically if the old detector is not uninstalled
within one hour.
A missing message is reported in fault view if the old detector is uninstalled but
the new one is not installed within one hour.
.
.
.
.
.
.