9.2 Install panel

9.3 Startup panel

9.4 General commissioning steps

9.4.1 Auto configure detector line

Building Technologies
Fire safety
w The fire control panel FC361-xx is mounted.
1. Insert the cables for the detector lines and the mains supply into the panel and
connect them to the panel. Refer to chapter 'Power supply - mains voltage
[➙ 29]'.
2. Place the batteries and connect them to the power supply. Refer to chapter
'Battery [➙ 30]'.
1. Connect the cables for the detector lines.
2. Connect the power supply (mains and batteries).
a The panel executes first startup.
a During startup, the fault LED and system fault LED are on and the display
shows no information.
3. Wait until the display indicates the selection of the country and language.
4. Press
/
to select your country and press
5. Press
/
to select your language and press
a The panel starts loading your country and language default settings.
a The display indicates the progress status.
6. Wait for the start-up progress to be terminated.
a The panel is ready for commissioning.
NOTICE
Report 'configuration fault' during the first system startup
The detector line is detected as two stubs during the first system startup even if
they are connected as a loop.
Carry out 'Auto configuration' during commissioning and the fault disappears.
Refer to chapter 'auto configure detector line [➙ 89]'.
After finishing auto configuration:
All devices on the detector line are read in and added to the detector line as
per the topology.
All the devices are configured with the default settings. (see 'Appendix D:
Default setting for panel/devices [➙ 117]')
Some devices are assigned to corresponding zones automatically. (see
'Appendix B: Zone type list [➙ 115]')
Create default control logics as per predefinition.
Commissioning
Install panel
and confirm with
.
and confirm with
.
97 | 124