4.4.2 Electrical data

A6V10421795_en--_k
Rating detector line
Operating voltage
Operating current
Line resistance/capacitance
Monitored for earth fault
Monitored for open/short circuit
Sounder lines on mainboard
Voltage/current
EOL element
AUX. power output
Configurable IOs on mainboard
Voltage/current
Outputs on output card (4M) FCA3602-Z1
Voltage/current (max. per output)
EOL element
Additionally for outputs on output card (4M) FCA3602-Z1 with the
functionality 'creeping open/short'
Line resistance
Sounder voltage
Relay outputs on mainboard
Power supply
Mains voltage
Mains fuse
Power consumption
Max. nominal output current with battery
charging, I
max a
Max. nominal output current without battery
charging, I
max b
Min. output current
System supply voltage
Mains failure delay
Battery low discharge cut off
Temperature compensation
System description
Technical data
DC 12...33 V
Max. 0.5 A
Max. 240 Ω/Max. 500 nF
Yes
Yes
DC 24 V/0.5 A
1
Resistor 2.2 kΩ/1 W/0.5 %
DC 24 V/0.2 A
2
DC 24 V/0.1 A
DC 24 V/1.0 A
3
Resistor 2.2 kΩ/1 W/0.5 %
Max. 74.3 Ω
Min. DC 16 V
DC 60 V/2.0 A
AC 97...127 V
AC 196...253 V
AC 250 V/2.5 AT
70 W
0.9 A
2.5 A
0.05 A
DC 20.5...28.6 V
1 min., 5 min., 10 min., 29 min.
DC 20.5...21 V
Yes
4