Commissioning
9
General commissioning steps

9.4.2 Configure the system manually

98 | 124
Building Technologies
Fire safety
Modify using 'FC360 Panel Configurator'
1. Connect PC to the panel. Refer to chapter 'Connect PC to panel [➙ 95]'.
2. Open a web browser.
3. Enter web address with 'fc360.siemens.com' and press <Enter>.
a 'FC360 Panel Configurator' is open.
4. Enter access level 3 password to login to level 3.
5. Modify configuration as needed.
a Generally the following configuration may be modified in 'FC360 Panel
Configurator':
Customer texts
Properties and the parameter settings
Allocation of zones and sections
Control logics
6. After finishing modification, click 'Apply'.
a A confirmation window is open.
7. Click 'OK' to download the modified configuration to the panel. (The panel is at
access level 3.)
a The panel restarts automatically.
a The configuration finishes.
A6V10421795_en--_g