Commissioning
9
General commissioning steps
9.4.2 Configure the system manually
98 | 124
Building Technologies
Fire safety
Modify using 'FC360 Panel Configurator'
1. Connect PC to the panel. Refer to chapter 'Connect PC to panel [➙ 95]'.
2. Open a web browser.
3. Enter web address with 'fc360.siemens.com' and press <Enter>.
a 'FC360 Panel Configurator' is open.
4. Enter access level 3 password to login to level 3.
5. Modify configuration as needed.
a Generally the following configuration may be modified in 'FC360 Panel
Configurator':
–
Customer texts
–
Properties and the parameter settings
–
Allocation of zones and sections
–
Control logics
6. After finishing modification, click 'Apply'.
a A confirmation window is open.
7. Click 'OK' to download the modified configuration to the panel. (The panel is at
access level 3.)
a The panel restarts automatically.
a The configuration finishes.