ASC-1 Connections and Ratings
Electrical ratings:
SPEAKER ZONE DECIBEL LOSS
for 25.2V RMS, 35W load
Length
14 AWG
(feet)
200
400
600
800
1000
Technical Manuals Online! - http://www.tech-man.com
Gauge
16 AWG
18 AWG
(loss in decibels)
0.2
0.3
0.6
0.5
0.7
1.1
0.7
1.1
1.6
0.9
1.5
2.2
1.2
1.8
2.7
firealarmresources.com
Electrical connections:
SPEAKER ZONE DECIBEL LOSS
for 70.7V RMS, 25W load
Gauge
Length
16 AWG
(feet)
(loss in decibels)
200
0.04
400
0.07
600
0.11
800
0.14
1000
0.18
18 AWG
0.06
0.11
0.17
0.22
0.27
4 - 5