8.4.3 Read in

Building Technologies
Fire safety
The 'Read in' operation must be executed after performing one of the following
actions:
Change topology of detector line, e.g. merge two stubs into one loop.
Add new device(s).
1. Press
on the keypad.
a The 'Main menu' window is open.
2. Select 'Engineering' and press
a The 'Engineering' window is open.
3. Select 'Detector line' and press
a The 'Detector line' window is open.
4. Select 'Read in' and press
a The 'Read in' window is open.
5. Select the first detector line and press
a A confirmation dialog window is open.
6. Press
to confirm.
a The detector line starts to read in.
a The message 'Read in is ongoing...' is displayed. The panel returns to previous
status after reading in.
a The panel reports an 'Unassigned Zone' fault for each new device if new
devices are connected. The new devices need to be assigned to zones by
'FC360 Panel Configurator'.
When two stubs are merged into one loop, always select the first stub in step 5.
The second stub is adopted automatically.
When a sub-stub is connected to a loop, the topology is also detected as a loop.
The 'Read in' operation is requested to add the new sub-stub.
The 'Read in' operation does not succeed if a device is missing.
Panel need to be restarted manually after read in. Otherwise, the devices on the
detector line are under configuration mode and cannot report fault event.