Description of the I/O Modules

Binary Input Modules

Types of Binary Input Modules and Terminal
Socket
Type
Description
CLIOP823 Panel Bus binary input module
CLIOL823 L
W
Bus binary input
ON
ORKS
module
XS823
Terminal socket
XSU823
Table 50 LION Binary Input Modules
Features
• 12 binary inputs
• 12 configurable status LEDs (green/red, yellow/OFF)
• Binary inputs can be used as
– Static digital inputs as dry-contacts (default)
– Fast totalizers (up to 20 Hz)
1
Fig. 71
CLIOP823A Binary Input Module with terminal
socket
Legend
1
Service button S1
2
Hex switch S2
3
Input LEDs
4
Service LED
5
Power LED
Functionality of service LED and power LED: see Table 77
to Table 79 on page 78 and following.
EN1Z-0921GE51 R0709
Housing
Light gray
Dark gray
Light gray
2
3
4 5
Terminals
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
BI1
BI2
BI3
BI4
BI5
BI6
1
2
3
4
5
GND
GND GND GND GND GND GND GND GND GND GND GND
13
14
15
16
17
18
Fig. 72
Terminal assignment and internal connections of
binary input modules
Ter-
Signal
COMMENT
minal
2-wire communication bus
71, 75
COM a
(LON/Panel Bus)
2-wire communication bus
72, 76
COM b
(LON/Panel Bus)
73, 77
24 V~
Power supply
74, 78
24 V~0
Power supply
1...12
BI1...BI12 Binary inputs 1...12
Ground. All grounds are connected
13...24
GND
internally to each other.
Shield connection (functional earth),
25, 26
internally connected to the DIN rail.
Table 51 Description of binary input module terminals
Notes
• Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a L
L
W
requires a resistor and capacitor.
ON
ORKS
• If additional shield terminals are needed, the
XS814 Auxiliary Terminal Package can be installed.
50
LION System
BI7
BI8
BI9
BI10
BI11
BI12
6
7
8
9
10
11
12
19
20
21
22
23
24
W
shield, since
ON
ORKS
COM
75
A
COM
76
B
24
77
V~
24
78
V~0
25 26

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents