One instance of the L
M
ON
been assigned per input of the CLIOL824A/CLIOLR824A
Relay Output Module.
Each output object has its own configuration properties,
except for heartbeat configuration, which will be shared
among all objects.
Open Loop Actuator Object
(LonMark Object Type 3)
nviDoSwitch[x]
|1
SNVT_switch
nciDoConfig[x]
UCPT_DOConfig
nciRcvHrtBt[x]
SCPTmaxRcvTime
Fig. 107
L
M
output object
ON
ARK
open-loop sensor object has
ARK
nvoDoActPosnFb[x]
#1
SNVT_switch
Configuration
Parameter
Value File
Relay Output Command – nviDoSwitch[ ]
This network variable is used to drive the relay output.
It is typically bound to a L
output level ON/OFF, respectively 0 ... 100 %.
Valid Range
Value
N/a
0
0.5 ... 100 %
N/a
Table 70 Relay output command values
Default Value
Value = 0
State = -1
Start-up Behavior
At start-up, i.e., power-up or reset, all nvi's will be initialized
with INVALID, leading the actuator to drive to the configured
safety position after 1 minute.
Receive Heartbeat
The default configuration for "Receive Heartbeat" is 300 sec.
If no nvi update is received during this time, the field devices
will go to their configured safety positions.
73
LON Software Interface Description
W
control device issuing an
ON
ORKS
State
Action
0
OFF
1
OFF
Outputs are switched
1
according to actual output
type configuration
INVALID:
-1
as defined for failure behavior
EN1Z-0921GE51 R0709