Wiring and Setting Up the System
Wiring and Setting Up the System
General Safety Considerations
• When connecting the CLLIONLC01 or LION I/O modules,
both VDE, National Electric Code (NEC) or equivalent,
and any local regulations concerning grounding and zero
voltage must be observed.
• Electrical work should be carried out by a qualified
electrician.
• The electrical connections must be made at the terminal
blocks. The corresponding connection diagrams are
located on the individual controller module and
I/O modules.
• For Europe only: To comply with CE requirements,
devices with a voltage in the range of 50 ... 1000 VAC or
75 ... 1500 VDC, which are not provided with a supply
cord and plug or with other means for disconnection from
the supply having a contact separation of at least 3 mm
in all poles, must have the means for disconnection
incorporated in the fixed wiring.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet.
►
Disconnect the power supply before making connections
►
to or removing connections from terminals of controller or
I/O modules.
Do not use spare terminals as wiring support points.
►
Do not reconnect the power supply until you have
►
completed the installation.
Observe precautions for handling electrostatic sensitive
►
devices.
EN1Z-0921GE51 R0709
Wiring Push-in Terminals
The terminal sockets of the pluggable I/O modules are
available in versions (...82...) featuring convenient push-in
terminals for easy wiring. The CLIOP830A likewise features
push-in terminals.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
Solid conductor H05/07) V-U
Stranded conductor H05(07) V-K
Stranded conductor with wire end
ferrules (without plastic collar)
Stripping length
Table 22 Push-in terminals wiring specifications
Wiring Screw-Type Terminals
The terminal sockets of the pluggable I/O modules are also
available with screw-type terminals.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
Solid conductor H05/07) V-U
Stranded conductor H05(07) V-K
Stranded conductor with wire end
ferrules (without plastic collar)
Stripping length
Table 23 Screw-type terminals wiring specifications
24
LION System
2
0.14 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
8.0 +1.0 mm
2
0.14 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
11.0 +1.0 mm