LION System
C-Bus Termination Switch S1
The CLLIONLC01 features a 3-position C-Bus termination
switch S1.
This switch must be set in accordance with the given C-Bus
configuration.
S1
9.6k
al l
76k
mi d
76k
end
C-Bus
Fig. 57
C-Bus termination switch
Switch
Baud rate
setting S1
Up to 9600 baud (default setting)
9.6k all
76k mid
Up to 76800 baud without bus termination
Up to 76800 baud with bus termination
76k end
controller at the end of the C-Bus
Table 40 CLLIONLC01 C-Bus termination switch S1
settings
Memory
Memory
Size
SRAM
512 KB
Flash
2 MB
EPROM
128 KB
Table 41 CLLIONLC01 memory
Note
The CLLIONLC01 does not contain a battery. RAM (data
and realtime clocktime) is buffered for 3 days by a super
capacitor.
Usage
For controller application,
modem trend and firmware
RACL application: 128 KB
Total application: 192 KB
Firmware (1 MB) and
application (1 MB) storage
For bootstrap loader