Honeywell CENTRA LINE LION CLLIONLC01 Installation & Commissioning Instructions page 37

Table of Contents

Advertisement

LION System
Alarm and Power LEDs
The CLLIONLC01 is equipped with an alarm LED and a
power LED.
Fig. 54
Alarm LED (1) and power LED (2)
Alarm LED (1, red)
Off
Normal operation
On
Watchdog alarm output is powered
• The controller has encountered a
hardware problem
• The application has a fault
• The controller has been powered up
without an application or the operator has
manually stopped the application,
e.g., using XL-Online.
In this case, the LED will light up
13 minutes after power-up without
application
Flashing
The watchdog alarm output has not yet been
powered, although the controller has
encountered a problem.
The controller performs a warm start.
If the problem persists, the LED will become
lit constantly, see above.
See section "Troubleshooting" on page 74.
Table 33 Controller alarm LED
Power LED (2, green)
On
Flashing
Goes out
briefly
Table 34 Controller power LED
1
2
Watchdog
Watchdog status
Status
Failure (= alarm)
Normal operation
Table 35 Watchdog status 4
Permissible Load of Normally Closed Contact
(Terminal 4)
Per normally
closed
contact
(terminal 4)
Table 36 Permissible load of terminal 4
37
Description of the CLLIONLC01
Normal operation
One or more of the internal voltage
supplies are outside of the permissible
ranges.
The controller stops operation.
Check wiring or see section "Trouble-
shooting" on page 74.
• The operator has activated the reset
button
• The controller is performing a warm
start
Signal on terminal 4
24 V
0 V
Max. load
19...29 VAC
current at cos φ ≥ 0.95: 0.5 A,
current at cos φ ≥ 0.6: 0.5 A
19...29 VDC
0.5 A resistive or inductive
EN1Z-0921GE51 R0709
Min.
current
10 mA

Hide quick links: