Description of the CLLIONLC01
Modem Interface
The controller module is equipped with a modem interface
for the connection of a modem or an ISDN terminal adapter.
Fig. 55
Modem interface, Tx LED (1) and Rx LED (2)
Modem LEDs on RJ45 socket
Tx (1) flickering The controller is transmitting data to the
HMI, e.g., CLMMI00N22 or
CLMMI00N31
Rx (2)
The controller is receiving data from the
flickering
HMI
Table 37 HMI interface LEDs
Modem Signals on RJ45 socket
Pin
Signal type
1
Carrier detect
2
Receive
3
Transmit
4
Data terminal ready
5
Signal ground
6
-
7
5 V
8
Clear to send
Table 38 Signals of the modem interface
Communication Speed
Default setting: 9600 baud
The communication speed can be set to as high as
38.4 Kbaud, e.g., using the CLMMI00N22 or CLMMI00N31
or a laptop with XL-Online, see Appendix 2.
EN1Z-0921GE51 R0709
12
3
45
6
78
Tx
Rx
1
2
38
I/O Bus Switch S2
The CLLIONLC01 features a 2-position I/O Bus switch S2.
I/O Bus switch S2 must be set in accordance with the kind
of I/O modules connected to communication terminals
71, 72 and 75, 76 of the controller module.
Terminals 71, 72 and 75, 76 must be all connected either to
Panel Bus I/O modules or to L
The default setting is Panel.
S2
Panel
LO N
I/O Bus
Fig. 56
I/O Bus switch S2
Communication
L
W
Bus only
ON
ORKS
Panel Bus and L
W
ON
ORKS
L
W
B
modules connected to
ON
ORKS
US
terminals 11 .... 14 of the controller
Panel Bus connected to terminals 71, 72
or 75, 76 of the controller
Table 39 I/O Bus switch settings
LION System
W
Bus I/O modules.
ON
ORKS
S2 setting
LON
Bus
Panel
Panel