Cliol823A Binary Input Module - Honeywell CENTRA LINE LION CLLIONLC01 Installation & Commissioning Instructions

Table of Contents

Advertisement

LON Software Interface Description

CLIOL823A Binary Input Module

One instance of the L
M
ON
been assigned per input of the CLIOL823A Binary Input
Module.
Each digital input object has its own configuration
properties, except for heartbeat configuration, which will be
shared among all objects.
Open Loop Sensor Object
(LonMark Object Type 1)
nciDiConfig[x]
UCPT_DIConfig
nciSndHrtBt
SCPTmaxSendTime
Fig. 105
L
M
digital input object
ON
ARK
Transmission
These variables are transmitted immediately when its value
has been changed by a higher rate than the configured
"send on delta" (in the case of the totalizer, "send on delta"
has a default value of 5 counts).
These variables are also transmitted as a heartbeat output
on a regular basis as dictated by the maximum send time
(nciSndHrtBt) (default = 0 = disabled) configuration variable.
Default Service Type
The default service type of these variables is
unacknowledged.
EN1Z-0921GE51 R0709
open-loop sensor object has
ARK
nvoDiSwitch[x]
|1
SNVT_switch
nvoDiCount[x]
#1
SNVT_count
Configuration
Parameter
Value File
Fast Binary Input – nvoDiSwitch[ ]
This network variable output represents the logical state of a
fast binary input connected to the binary input terminals.
Valid Range
Logical input state Value
ON
OFF
Not configured
Table 68 Slow digital input values
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
Value = 0
State = -1
Totalizer Count – nvoDiCount[ ]
This network variable output indicates the total number of
transitions from 0 to 1 since the last reset due to power-up
or network reset.
Valid Range
Fig. 106
Totalizer
State
For totalizer counts
For power-up/reset
Table 69 Totalizer counts
Power-up/Reset
After power-up and reset, the value 0xFFFF = 65535 will be
sent to the network to indicate that previous count values
have been lost due to a reset.
72
LION System
State
100 %
1
0 %
0
0 %
-1
Value
0 ... 65534
65535

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents