Troubleshooting

I/O Modules Troubleshooting

Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the
inputs/outputs of the ...821, ...822, ...823 I/O modules.
Replace the problem I/O module with another module of the same kind.
– If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring.
– If the problem is solved, this is an indication that the I/O module was defective.
For troubleshooting purposes, the following features can be used:
Power LED (all LION I/O modules)
Service LED (all LION 800 I/O modules)
Service button (pluggable LION I/O modules, only)
In addition, a module-specific troubleshooting may be necessary.
Power LED of I/O Modules
case
Power LED
1
ON
2
OFF
3
Flashing continuously
Table 77 Power LED of I/O modules
EN1Z-0921GE51 R0709
Meaning
I/O module is powered
No power
If the I/O module's service LED is likewise
flashing, the I/O module is in the boot mode
Remedy
No action necessary
Check power supply
Wait until rebooting (firmware
download) has been completed
78