Honeywell CENTRA LINE LION CLLIONLC01 Installation & Commissioning Instructions page 59

Table of Contents

Advertisement

LION System
Terminals
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
Actuator 1
Actuator 2
11
31
21
NO
NO
NO
12
32
22
NC
NC
NC
13
33
23
COM
COM
COM
14
34
24
CON
CON
CON
Cross connector (can be removed, as desired)
Fig. 81
Terminal assignment and internal connections of
floating output module
Ter-
Signal
Comment
minal
71, 75
2-wire communication bus (LON/Panel Bus)
COM a
72, 76
2-wire communication bus (LON/Panel Bus)
COM b
73, 77
Power supply
24 V~
74, 78
Power supply
24 V~0
11
Floating relay 1 N.O. contact
REL1 N.O.
12
Floating relay 1 N.C. contact
REL1 N.C.
13
Floating relay 1 common contact
R1 COM
For connection of floating relay 1 common
14
R1 COM
via cross connector*
21
REL2 N.O.
Floating relay 2 N.O. contact
22
Floating relay 2 N.C. contact
REL2 N.C.
23
Floating relay 2 common contact
R2 COM
For connection of floating relay 2 common
24
R2 COM
via cross connector*
31
Floating relay 3 N.O. contact
REL3 N.O.
32
Floating relay 3 N.C. contact
REL3 N.C.
33
Floating relay 3 common contact
R3 COM
For connection of floating relay 3 common
34
R3 COM
via cross connector*
41
Floating relay 4 N.O. contact
REL4 N.O.
42
Floating relay 4 N.C. contact
REL4 N.C.
43
Floating relay 4 common contact
R4 COM
For connection of floating relay 4 common
44
R4 COM
via cross connector*
51
Floating relay 5 N.O. contact
REL5 N.O.
52
REL5 N.C.
Floating relay 5 N.C. contact
53
Floating relay 5 common contact
R5 COM
For connection of floating relay 5 common
54
R5 COM
via cross connector*
61
Floating relay 6 N.O. contact
REL6 N.O.
62
Floating relay 6 N.C. contact
REL6 N.C.
63
Floating relay 6 common contact
R6 COM
For connection of floating relay 6 common
64
R6 COM
via cross connector*
Shield connection (functional earth),
25
internally connected to the DIN rail
* Do not connect by wire!
Table 58 Description of floating output module terminals
COM
A
COM
B
24
V~
24
V~0
Actuator 3
41
51
61
NO
NO
NO
42
52
62
NC
NC
NC
43
53
63
COM
COM
COM
44
54
64
CON
CON
CON
Status LED Behavior
The respective pair of status LEDs will display the following:
75
76
77
78
Mode
LED
Green LED
Auto
Red LED
Green LED
25
Override
Red LED
Table 59 LED behavior (for e.g., floating output 1)
Status LEDs with Manual Overrides
1
Fig. 82
Manual overrides (rotary knobs)
The floating output module is equipped with manual
overrides: one for each floating output. These rotary knobs
can be manually set to either "AUTO" or "0 ... 100%"
(infinitely adjustable).
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs.
Do not use excessive force. Adjust only by hand.
Manual Override in the AUTO Position
When a manual override of the CLIOPR825A is set to
AUTO, the following applies:
The output signal of the respective floating output (R1 +
R2 or R3 + R4 or R5 + R6) will be as commanded.
The respective pair of status LEDs will be ON/OFF as
commanded.
Manual Override in the Override Position (0...100%)
When a manual override of the CLIOPR825A is set to
0...100%, the respective floating output will drive to the set
position. The runtime depends upon the actuator runtime
configured using the engineering tool and on the actual
position.
59
Description of the I/O Modules
Actuator 1
Closing
Opening
ON
OFF
OFF
ON
Flashing
OFF
OFF
Flashing
3
2
EN1Z-0921GE51 R0709
Not
moving
OFF
OFF
Flashing
Flashing
0