Honeywell CENTRA LINE LION CLLIONLC01 Installation & Commissioning Instructions page 54

Table of Contents

Advertisement

Description of the I/O Modules
Terminals
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
Relay block 1
11
31
21
NO
NO
NO
12
32
22
NC
NC
NC
13
33
23
COM
COM
COM
14
34
24
CON
CON
CON
Cross connector (can be removed, as desired)
Fig. 76
Terminal assignment and internal connections of
relay output modules
Terminal Signal
Comment
2-wire communication bus
71, 75
COM a
(LON/Panel Bus)
2-wire communication bus
72, 76
COM b
(LON/Panel Bus)
73, 77
Power supply
24 V~
74, 78
Power supply
24 V~0
11
Relay 1 N.O. contact
REL1 N.O.
12
Relay 1 N.C. contact
REL1 N.C.
13
R1 COM
relay 1 common contact
For connection of relay 1 common via
14
R1 COM
cross connector*
21
Relay 2 N.O. contact
REL2 N.O.
22
Relay 2 N.C. contact
REL2 N.C.
23
Relay 2 common contact
R2 COM
For connection of relay 2 common via
24
R2 COM
cross connector*
31
Relay 3 N.O. contact
REL3 N.O.
32
Relay 3 N.C. contact
REL3 N.C.
33
Relay 3 common contact
R3 COM
For connection of relay 3 common via
34
R3 COM
cross connector*
41
Relay 4 N.O. contact
REL4 N.O.
42
Relay 4 N.C. contact
REL4 N.C.
43
Relay 4 common contact
R4 COM
For connection of relay 4 common via
44
R4 COM
cross connector*
51
Relay 5 N.O. contact
REL5 N.O.
52
Relay 5 N.C. contact
REL5 N.C.
53
Relay 5 common contact
R5 COM
For connection of relay 5 common via
54
R5 COM
cross connector*
61
Relay 6 N.O. contact
REL6 N.O.
62
Relay 6 N.C. contact
REL6 N.C.
63
R6 COM
Relay 6 common contact
For connection of relay 6 common via
64
R6 COM
cross connector*
Shield connection (functional earth),
25
internally connected to the DIN rail
* Do not connect by wire!
Table 54 Description of relay output module terminals
EN1Z-0921GE51 R0709
COM
A
COM
B
24
V~
24
V~0
Relay block 2
41
51
61
NO
NO
NO
42
52
62
NC
NC
NC
43
53
63
COM
COM
COM
44
54
64
CON
CON
CON
Permissible Loads
75
Per relay
76
output
77
module (total)
78
Per normally
open contact
Per normally
25
closed
contact
Table 55 Permissible loads of relay output modules
Notes
• In the case of voltages above 30 VAC/DC and if inductive
components are to be connected to relays switching
more often than once every 2 minutes, these com-
ponents must be prevented from causing harmful
interference to radio or television reception (conformance
with EN 55014).
• Max. voltage for UL 864-compliant applications is 24 V.
Status LED Behavior
Mode
Automatic mode, logical
state "ON"
Automatic mode, logical
state "OFF"
Override mode (setting "0")
Override mode (setting "1")
*As configured using the engineering tool.
Table 56 Relay output status LED behavior
Status LEDs with Manual Overrides
1
Fig. 77
Manual overrides (toggle switches)
The ... R 824A Relay Output Modules are equipped with
manual overrides: one for each relay output. These sliding
switches can manually be set to either "auto" or "0" or "1".
54
Max. load
19...250 VAC
current at cos φ ≥ 0.6: 12 A
1...29 VDC
12 A resistive, 3 A inductive
19...250 VAC
current at cos φ ≥ 0.6: 4 A
1...29 VDC
4 A resistive, 1 A inductive
19...250 VAC
current at cos φ ≥ 0.95: 2 A,
current at cos φ ≥ 0.6: 1 A
1...29 VDC
4 A resistive, 1 A inductive
LED
N.O.*
(direct)
ON
ON
OFF
OFF
Flashes
OFF
Flashes
ON
5
2
4
6
3
LION System
Min. load
50 mW
50 mW
Relay output
N.C.*
(reverse)
OFF
ON
ON
OFF
--1
--0
--AUTO
!