8.7.7 MP Fault Assigned to Alarm

In this menu you can define, which alarms should be activated by a fault at the measuring point. If the fault is
cleared, the alarm is automatically reset.
Symbol
Description
Alarm
Assignment of
Fault
MP fault to
alarm

8.7.8 Alarm Assigned to Alarm Relay

Each of the four alarms can be assigned to any alarm relay 1 – 5 registered in the menu Relay Parameters by
entering the relay address right under the alarm. One alarm relay can be assigned to multiple alarms. Unused
alarms aren't assigned.
The fault relay can also be used for alarm message (address 3). The relay has to be registered in the menu
Relay Parameters. The fault message function, however, remains unaffected.
Symbol
Description
Alarm
A1 A2 A3 A4
Assignment of
alarm relay

8.7.9 MP Assigned to Analog Output

The measuring signal can be assigned to an analog output by entering the address of the analog output
instead of x. The analog output is configured in the menu System Parameters, AO Function.
Symbol
Description
X
Address AO
®
PolyGard
is a registered trademark of MSR
Phone 0049(0)8531/9004-0

Fax: 0049(0)8531/9004-54

MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
®
2
Default
Function
Indication of the alarms 1 to 4; you can define with 1 for each
alarm that the alarm should be activated in case of MP fault.
0 = Alarm isn't activated in case of MP fault.
0 0 0 0
1 = Alarm is activated in case of MP fault.
Default
Function
Presentation of the alarms 1 to 4; you can assign an alarm relay to
each alarm by setting a relay address.
A1 = X
A2 = X
X = Assignment of an alarm relay (relay address) to an alarm
A3 = X
A4 = X
Default
Function
X = Assignment of an analog output by entering the AO address
Page
Alarm
- 1234
Fault
- 0100
A1
A2
A3
A4
1
0
0
0
Analog Output
x