Paytec Eagle User Manual page 82

Changegiver
Table of Contents

Advertisement

Reset errors?
Status sensor
F4 4,--
F5 0,--
Status separator
S1 0,--
S2 0,--
Full tubes
AD 0
BE 0
CF 0
Motors
AD 1
BE 1
CF 1
Ejectors
A 1
B 1
C 1
Ejectors
D 1
E 1
F 1
N The errors memorized are not cleared.
Y All the errors memorized are cleared.
Clear the coin jam (if any). If the error is repeated, contact Paytec
Customer Service.
Only-read message.
The analogue values are displayed for the optical sensors:
F4 is cashbox sensor 1
F5 is cashbox sensor 2
While this message is displayed, a test can be performed to switch level for
sensor F4.
Press A, B or C to activate the door of cashbox 1 and switch the level of
sensor F4 from level 4,--V to level 0,--V.
Press D, E or F to activate the door of cashbox 2. The status of sensor F5
must remain at level 0,--V.
In the case of abnormal values, contact Paytec Customer Service.
Only-read message.
The analogue values are displayed for the separator sensors:
S1 is separator sensor 1
S2 is separator sensor 2
While this message is displayed, the separator mechanism can be tested.
Press A, B or C to move the mechanism towards tubes ABC.
Press D, E or F to move the mechanism towards tubes DEF.
When the test is over, press
In the case of abnormal values, contact Paytec Customer Service.
Only-read message.
The digital values are displayed for the sensors detecting coins falling in the
tubes. The sensors are referred to the 2 tubes on the same line (Fig.17).
AD
sensors controlling coins falling in tubes A and D.
BE
sensors controlling coins falling in tubes B and E.
CF
sensors controlling coins falling in tubes C and F.
While this message is displayed and a sensor is darkened (e.g. by a coin),
its logic level switches from 0 to 1.
Only-read message.
The digital values are displayed for the sensors of the ejector motors.
In standby position, the logic level is 1.
The sensors are referred to the 2 ejectors moved by the same motor shaft
nail (Fig.13).
Only-read message.
The digital values are displayed for the sensors controlling the position of
each ejector for tubes A, B, C.
1 = standard value in standby position (sensors darkened).
0 = ejector is not in its correct position.
Only-read message.
The digital values are displayed for the sensors controlling the position of
each ejector for tubes D, E, F.
1 = standard value in standby position (sensors darkened).
0 = ejector is not in its correct position.
82
standard value in standby: >4.5V.
standard value in standby: <0.2V.
standard value in standby: <0.2V.
standard value in standby: <0.2V.
(P6000) to reset the separator position.