Configure digital communications
April 2019
Output Action. This is designed to make it easier to configure the transmitter for legacy behavior.
Always verify mA Output Action after setting HART Address.
9.1.2 Configure HART variables (PV, SV, TV, QV)
Display
Menu > Configuration > Inputs/Outputs > Channel A > HART Settings > HART Variables
Device Tools > Configuration > Communications > Communications (HART) > Variable Assignment
ProLink III
Field Communicator
Configure > Manual Setup > Inputs/Outputs > Variable Mapping
The HART variables are a set of four variables predefined for HART use. The HART variables include the
Primary Variable (PV), Secondary Variable (SV), Tertiary Variable (TV), and Quaternary Variable (QV). You can
assign specific process variables to the HART variables, and then use standard HART methods to read or
broadcast the assigned process data.
Note
The Tertiary Variable and Quaternary Variable are also called the Third Variable (TV) and Fourth Variable (FV).
Restriction
The Primary Variable is always the process variable assigned to mA Output 1. If you change either of these
assignments, the other is changed automatically.
The Secondary Variable and Tertiary Variable are not tied to any outputs. This is different from previous
Micro Motion Coriolis transmitters.
Procedure
Assign variables to the PV, SV, TV, and QV as desired.
Options for HART variables
Process variable
Standard
Mass flow rate
Volume flow rate
Gas standard volume flow rate
Temperature
Density
External pressure
External temperature
Totalizers and inventories
Current value of any totalizer
Current value of any inventory
Diagnostics
Velocity
110
PV
SV
Configuration and Use Manual