Internal Variables - WAGO 750-341 Manual

Ethernet tcp/ip
Hide thumbs Also See for 750-341:
Table of Contents

Advertisement

146 •

Internal Variables

Function Code FC23 (Read/Write multiple registers)
Start address
0x0000
0x0200
0x1000
0x2000
0x3000
0x8000
6.5 Internal Variables
Address Access
0x1000
0x1001
0x1002
0x1003
0x1004
0x1005
0x1006
0x1007
0x1008
0x1009
0x100A R/W
0x100B
0x1020
0x1021
0x1022
0x1023
0x1024
0x1025
0x1028
0x1029
0x102A R
0x1030
0x1031
End address
0x01FF
0x03FF
0x1FFF
0x2FFF
0x7FFF
0x85F7
Length
Remark
(word)
R/W
1
Watchdog-Time read/write
R/W
1
Watchdog Coding mask 1-16
R/W
1
Watchdog Coding mask 17-32
R/W
1
Watchdog Trigger
R
1
Minimum Trigger time
R/W
1
Watchdog stop (Write sequence 0xAAAA, 0x5555)
R
1
Watchdog Status
R/W
1
Restart Watchdog (Write sequence 0x1)
RW
1
Stop Watchdog (Write sequence 0x55AA oder 0xAA55)
R/W
1
MODBUS -und HTTP- close at Watchdog Timeout
1
Watchdog Configuration
W
1
Save Watchdog parameter
R
1-2
LED Error Code
R
1
LED Error Argument
R
1-4
Number of analog output data in the process image (in bits)
R
1-3
Number of analog input data in the process image (in bits)
R
1-2
Number of digital output data in the process image (in bits)
R
1-4
Number of digital input data in the process image (in bits)
R/W
1
Boot configuration
R
9
MODBUS-TCP statistics
1
Number of TCP connections
R/W
1
Configuration MODBUS/TCP Timeout
W
1
Read out the MAC-ID of the coupler
Memory range
physical Outputs process image (1)
reserved
physical Outputs process image (2)
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP

Hide quick links: