54 •
Fieldbus Coupler 750-341
Process image
750-638
The 750-638 counter module has a total of 6 bytes of user data in both the
Input and Output Process Image (4 bytes of counter data and 2 bytes of
control/status). The two counter values are supplied as 16 bits. Each counter
has its own control/status byte. The following tables illustrate the Input and
Output Process Image, which has 4 words mapped into each image. Word
alignment is applied.
Offset
Offset
Pulse width Modules
750-511, /000-002
The above 750-511 Pulse Width modules have a total of 6 bytes of user data in
both the Input and Output Process Image (4 bytes of channel data and 2 bytes
of control/status). The two channel values are supplied as 16 bits. Each
channel has its own control/status byte. The following table illustrates the
Input and Output Process Image, which has 4 words mapped into each image.
Word alignment is applied.
Offset
Byte Destination
High Byte
Low Byte
0
-
1
D1
2
-
3
D3
Byte Destination
High Byte
Low Byte
0
-
1
D1
2
-
3
D3
Input and Output Process Image
Byte Destination
High Byte
Low Byte
0
-
C0/S0
1
D1
2
-
C1/S1
3
D3
Input Process Image
S0
Status byte of Counter 1
D0
Counter Value of Counter 1
S1
Status byte of Counter 2
D2
Counter Value of Counter 2
Output Process Image
C0
Control byte of Counter 1
D0
Counter Setting Value of Counter 1
C1
Control byte of Counter 2
D2
Counter Setting Value of Counter 2
Control/Status byte of Channel 1
D0
Data Value of Channel 1
Control/Status byte of Channel 2
D2
Data Value of Channel 2
Remark
Remark
Remark
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP