WAGO 750-341 Manual page 88

Ethernet tcp/ip
Hide thumbs Also See for 750-341:
Table of Contents

Advertisement

84 •
Fieldbus Coupler 750-341
LED Display
Fault code 2: -not used-
Fault argument
8
Timeout when writing data in the
EEPROM
9
Bus Coupler initialisation fault
10
RTC-Powerfail
11
Fault when reading out the time
from the RTC
12
Fault when writing the time in
the RTC
13
Error Clock-Interrupt
14
Maximum number of Gateway or
Mailbox I/O modules exceeded
Fault description
-
not used
Turn off the power supply of the
node, exchange fieldbus coupler
and turn the power supply on
again.
Turn off the power supply of the
node, exchange fieldbus coupler
and turn the power supply on
again.
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.
Turn off the power supply of the
node, reduce number of Gateway
or Mailbox I/O modules and turn
the power supply on again.
Trouble shooting
-
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP