122 •
Network Communication
Application Protocols
5.3.4.9.1
Configuration of SNMP
The SNMP is executed via Port 161. The port number for SNMP traps is 162.
This port number cannot be changed.
The configuration of SNMP is done via the web-based management system or
directly via SNMP. On the web page stored in the coupler, the name of the
device (sysName), the description of the device (sysDescription), the location
(sysLocation) and the contact person (sysContact) can be freely set under the
"Snmp" link. In addition, up to 2 trap managers can be specified.
5.3.4.9.2
Description of MIB II
The MIB II conformance to RFC1213 is divided into the following groups:
5.3.4.9.2.1
System Group
The System Group contains general information to the coupler.
Entry
sysDescr
sysObjectID
sysUpTime
sysContakt
sysName
sysLocation
sysServices
System Group
Interface Group
Address Translation Group
IP Group
IpRoute Table
IpNetToMediaTable
ICMP Group
TCP Group
UDP Group
SNMP Group
EGP Group
Access
read
read
read
read/write
read/write
read/write
read
Description
This entry contains the device identification. The
entry is fix coded on "WAGO 750-341".
This entry contains the authorizing identification of
the manufacturer.
This entry contains the time in hundredth seconds
since the last reset of the managements unit.
This entry contains the identification of the contact
person and contains information about the contact
possibilities.
This entry contains an administrative name for the
device.
This entry contains the physical place of installation
of the node.
This entry designates the quantity of services, which
this coupler contains.
WAGO-I/O-SYSTEM 750