WAGO 750-341 Manual page 175

Ethernet tcp/ip
Hide thumbs Also See for 750-341:
Table of Contents

Advertisement

7.3.2.16
Discrete Output Point Extended 1..3 (6A
Same as the Discret Input Point (66
digital inputs:
6A
6E
72
7.3.2.17
Analog Input Point Extended 1..3 (6B
Same as the Analog Input Point Class (67
extended analog inputs:
6B hex : Analog Inputs 256 ..510
6F hex : Analog Inputs 511 ..765
73 hex :
7.3.2.18
Analog Output Point Extended 1..3 (6C
Same as the Analog Input Point Class (68
extended analog outputs:
6C hex : Analog Outputs 256 ..510
70 hex :
74 hex :
7.3.2.19
Module configuration (80
Class
Attribute ID Access Name
1
2
Instance 1..255 (0. to 254. Module)
Attribute ID Access
1
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
:
Digital Output 256 ..510
hex
:
Digital Output 511 ..765
hex
:
Digital Output 766 ..1020
hex
Analog Inputs 766 ..1020
Analog Outputs 511 ..765
Analog Outputs 766 ..1020
hex
Get
Revision
Get
Max Instance
Name
Get
ModulDescription
Ethernet/IP (Ethernet/Industrial Protocol)
6E
hex,
, however it contains the extended
hex)
6F
hex,
hex,
), however it contains the
hex
70
hex,
hex,
), however it contains the
hex
)
Data type
Description
UINT
Revision of this object
UINT
Max. number of instances
Data type
Description
Description of the connected
modules (module 0 = coupler)
Bit 0: Module has inputs
Bit 1: Module has outputs
Bit 8-14: Internal data width in bit
WORD
Bit 15: 0/1 Analog/digital module
At analog modules designate bits
0-14 the type of the module
displayed (e.g., 461 for the module
750-461).
Object model
72
)
hex,
hex
73
)
hex
74
)
hex
Default
value
1 (0x0001)
-
Default
value
-
• 171