WAGO 750-341 Manual page 75

Ethernet tcp/ip
Hide thumbs Also See for 750-341:
Table of Contents

Advertisement

Fig. 3.1-9: BootP table
2. Move the mouse pointer to the text line:
3. If you want to give your fieldbus node a name, delete the name "node1" and
4. To assign the coupler a desired IP address, mark the IP address specified in
5. Because the second example is not necessary at present, insert a "#" in front
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
The examples mentioned above contain the following information:
Declaration
Meaning
node1,
Any name can be given for the node here.
node2
ht=1
Specify the hardware type of the network here.
The hardware type for ETHERNET is 1.
(The numbers are described in RFC1700)
ha=0030DE000100
Specify the hardware address or the MAC-ID of the ETHERNET
ha=0030DE000200
fieldbus coupler (hexadecimal).
ip= 10.1.254.100
Enter the IP address of the ETHERNET fieldbus coupler (decimal)
ip= 10.1.254.200
here.
T3=0A.01.FE.01
Specify the gateway IP address here.
Write the address for T3 in hexadecimal form and for gw in decimal
gw=10.1.254.1
form.
sm=255.255.0.0
In addition enter the Subnet-mask of the subnet (decimal), where the
ETHERNET fieldbus coupler belongs to.
No gateway is required for the local network described in this example.
Therefore, the first example: "Example of entry with no gateway" can be
used.
"node1:ht=1:ha=0030DE000100:ip=10.1.254.100" and mark the 12
character hardware address which is entered after ha=...
Enter the MAC-ID of your own network coupler.
enter any name in its place.
the example which is entered after ip=...
Replace it with the IP address you have selected.
of the text line of the second example: "# node2:hat=1:ha=003 0DE 0002
00:ip=10.1.254.200:T3=0A.01.FE.01", so that this line will be ignored.
Fieldbus Coupler 750-341
Starting up ETHERNET TCP/IP fieldbus nodes
• 71
p012908e