4 SETPOINT PROGRAMMING
GE Power Management
SPEED2 TRIP AT
ESCAPE
3.25 x FLA: 36.6 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
3.50 x FLA: 31.1 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
3.75 x FLA: 26.8 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
4.00 x FLA: 23.2 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
4.25 x FLA: 20.5 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
4.50 x FLA: 18.2 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
4.75 x FLA: 16.2 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
5.00 x FLA: 14.6 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
5.50 x FLA: 12.0 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
6.00 x FLA: 10.0 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
6.50 x FLA: 8.5 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
7.00 x FLA: 7.3 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
10.0 x FLA: 5.6 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
15.0 x FLA: 5.6 s
MESSAGE
SPEED2 TRIP AT
ESCAPE
20.0 x FLA: 5.6 s
MESSAGE
SPEED2 MIN ALLOWABLE
ESCAPE
LINE VOLTAGE: 80%
MESSAGE
SPEED2 ISTALL @ MIN
ESCAPE
Vline: 4.80 x FLA
MESSAGE
SPEED2 SAFE STALL @
ESCAPE
MIN Vline: 20.0 s
MESSAGE
SPEED2 ACL INTERSECT
ESCAPE
@ MIN Vline: 3.80 x FLA
MESSAGE
SPEED2 ISTALL @ 100%
ESCAPE
Vline: 6.00 x FLA
MESSAGE
469 Motor Management Relay
4.15 S14 TWO-SPEED MOTOR
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
Range: 70 to 95%; Step: 1
Message seen only if Voltage Dependent Curve Style is selected
Range: 2.00 to 15.00 x FLA; Step: 0.01
Message seen only if Voltage Dependent Curve Style is selected
Range: 0.5 to 999.9 sec; Step: 0.1
Message seen only if Voltage Dependent Curve Style is selected
Range: 2.00 to Istall@Min_Vline x FLA; Step: 0.01
Message seen only if Voltage Dependent Curve Style is selected
Range: 2.00 to 15.00 x FLA; Step: 0.01
Message seen only if Voltage Dependent Curve Style is selected
4
4-89