Current, Kw, Kvar, Kva Demand - GE MOTOR MANAGEMENT RELAY 469 Instruction Manual

Table of Contents

Advertisement

4.12 S11 MONITORING
S CURRENT DEMAND
S [ENTER] for more
S kW DEMAND
S [ENTER] for more
4
S kvar DEMAND
S [ENTER] for more
S kVA DEMAND
S [ENTER] for more
4-74
ð
CURRENT DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
CURRENT DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
CURRENT DEMAND
ESCAPE
LIMIT: 100 A
MESSAGE
CURRENT DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
ð
kW DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
kW DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
kW DEMAND
ESCAPE
LIMIT: 100 kW
MESSAGE
kW DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
ð
kvar DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
kvar DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
kvar DEMAND
ESCAPE
LIMIT: 100 kvar
MESSAGE
kvar DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
ð
kVA DEMAND
ENTER
PERIOD: 15 min.
ESCAPE
kVA DEMAND
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
kVA DEMAND
ESCAPE
LIMIT: 100 kVA
MESSAGE
kVA DEMAND
ESCAPE
ALARM EVENTS: Off
MESSAGE
469 Motor Management Relay
4 SETPOINT PROGRAMMING

4.12.3 CURRENT, KW, KVAR, KVA DEMAND

Range: 5 to 90 min., step 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: 10 to 100000 A, step 1
Range: On, Off
Range: 5 to 90 min., step 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: 1 to 50000 kW, step 1
Range: On, Off
Range: 5 to 90 min., step 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: 1 to 50000 kvar, step 1
Range: On, Off
Range: 5 to 90 min., step 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: 1 to 50000 kVA, step: 1
Range: On, Off
GE Power Management