GE MOTOR MANAGEMENT RELAY 469 Instruction Manual page 235

Table of Contents

Advertisement

6 COMMUNICATIONS
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 5 of 14)
FORMAT
TYPE
DEFINITION
CODE
14 General Sw. D
15 Capture Trace
16 Simulate Pre-Fault
17 Simulate Fault
18 Simulate Pre-Fault...Fault
FC111
Unsigned
TRIP RELAYS
16 bit integer
0 Trip
1 Trip & Aux2
2 Trip & Aux2 & Aux3
3 Trip & Aux3
FC112
Unsigned
NOT DEFINED
16 bit integer
0
1
FC113
Unsigned
ALARM RELAYS
16 bit integer
0 Alarm
1 Alarm & Aux2
2 Alarm & Aux2 & Aux3
3 Alarm & Aux3
4 Aux2
5 Aux2 & Aux3
6 Aux3
FC114
Unsigned
COUNTER TYPE
16 bit integer
0 Increment
1 Decrement
FC115
Unsigned
ALARM / TRIP TYPE SELECTION
16 bit integer
0 Off
1 Latched
2 Unlatched
FC116
Unsigned
SWITCH TYPE
16 bit integer
0 Normally Open
1 Normally Closed
FC117
Unsigned
RESET MODE
16 bit integer
0 All Resets
1 Remote Reset Only
2 Keypad Reset Only
GE Power Management
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 6 of 14)
FORMAT
TYPE
CODE
FC118
Unsigned
16 bit integer
FC119
Unsigned
16 bit integer
FC120
Unsigned
16 bit integer
FC121
Unsigned
16 bit integer
FC122
Unsigned
16 bit integer
469 Motor Management Relay
6.4 MEMORY MAP
DEFINITION
SHORT CIRCUIT RELAYS
0 Trip
1 Trip & Aux2
2 Trip & Aux2 & Aux3
3 Trip & Aux3
4 Aux2
5 Aux2 & Aux3
6 Aux3
BACKUP RELAYS
0 Aux2
1 Aux2 & Aux3
2 Aux3
RTD TYPE
0 100 Ohm Platinum
1 120 Ohm Nickel
2 100 Ohm Nickel
3 10 Ohm Copper
RTD APPLICATION
0 None
1 Stator
2 Bearing
3 Ambient
4 Other
RTD VOTING SELECTION
1 RTD #1
2 RTD #2
3 RTD #3
4 RTD #4
5 RTD #5
6 RTD #6
7 RTD #7
8 RTD #8
9 RTD #9
10 RTD #10
11 RTD #11
12 RTD #12
6