4 SETPOINT PROGRAMMING
S FORCE OUTPUT RELAY
S [ENTER] for more
The output relays can be independently forced in static or dynamic mode. In static mode the selected relay will
operate as long as it is in the "Enabled" state. Only when the user enters "Disabled" will the selected relay reset. In
dynamic mode the user specifies the operate time (1 to 300 seconds) and the selected relay will operate for the
specified duration.
The FORCE OUTPUT RELAY option is NOT allowed when the selected relay output is already active due to trip or
alarm condition, when the 469 is in start block condition, or when the 469 is not in service.
IMPORTANT NOTE:
• The forced relay will override any trip or alarm conditions.
NOTE
(i.e. when the relay is forced and trip occurs, the relay will still be enabled when the trip condition is
reset)
Control power loss in the 469 will reset all forced relays.
GE Power Management
ð
OPERATE R1
ENTER
RELAY: Disabled
ESCAPE
R1 OPERATE
ESCAPE
TIME: Static
MESSAGE
OPERATE R2
ESCAPE
RELAY: Disabled
MESSAGE
R2 OPERATE
ESCAPE
TIME: Static
MESSAGE
OPERATE R3
ESCAPE
RELAY: Disabled
MESSAGE
R3 OPERATE
ESCAPE
TIME: Static
MESSAGE
OPERATE R4
ESCAPE
RELAY: Disabled
MESSAGE
R4 OPERATE
ESCAPE
TIME: Static
MESSAGE
OPERATE R5
ESCAPE
RELAY: Disabled
MESSAGE
R5 OPERATE
ESCAPE
TIME: Static
MESSAGE
469 Motor Management Relay
4.5 S4 OUTPUT RELAYS

4.5.3 FORCE OUTPUT RELAY

Range: Disabled, Enabled
Range: Static, 1 to 300 s
Range: Disabled, Enabled
Range: Static, 1 to 300 s
Range: Disabled, Enabled
Range: Static, 1 to 300 s
Range: Disabled, Enabled
Range: Static, 1 to 300 s
Range: Disabled, Enabled
Range: Static, 1 to 300 s
4
4-25