It may be necessary to upgrade the revision code for a previously saved setpoint file after the 469 firmware has
been upgraded.
1. Establish communications with the relay.
2. Select the Actual > Product Information menu item and record the Main Revision identifier of the relay
firmware; for example, 30D270A8.000, where 270 is the Main Revision identifier and refers to firmware
version 2.70.
3. Select the File > Open menu item and enter the location and file name of the saved setpoint file to be
downloaded to the connected relay. When the file is open, the 469PC software will be in "File Editing"
mode and "Not Communicating".
4. Select the File > Properties menu item and note the version code of the setpoint file. If the version code of
the setpoint file (e.g. 2.6X) is different than the Main Revision code of the firmware (as noted in Step 1, as
270), use the pull-down tab to expose the available revision codes and select the one which matches the
firmware.
For example:
Firmware revision: 30D270A8.000
current setpoint file version: 2.6X
change setpoint file version to: 2.7X
5. Select the File > Save menu item to save the setpoint file in the new format.
6. See Section 8.3.3: LOADING SETPOINTS FROM A FILE for instructions on downloading this setpoint file
to the 469.
GE Power Management

8.3.5 UPGRADING SETPOINT FILES TO NEW REVISION

Figure 8–5: SETPOINT FILE VERSION