6.4 MEMORY MAP
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 3 of 14)
FORMAT
TYPE
DEFINITION
CODE
F20
32 bits
2's COMPLEMENT SIGNED LONG VALUE
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Note: -1 means "Never"
F21
16 bits
2's COMPLEMENT SIGNED VALUE
2 DECIMAL PLACES (Power Factor)
< 0 Leading Power Factor - Negative
> 0 Lagging Power Factor - Positive
Example: Power Factor of 0.87 lag is used as 87 (i.e. 0057)
F22
16 bits
TWO 8-BIT CHARACTERS
PACKED INTO 16-BIT UNSIGNED
MSB First Character
LSB Second Character
Example: String 'AB' stored as 4142 hex.
F24
32 bits
TIME FORMAT FOR BROADCAST
st
1
byte Hours (0 to 23)
nd
2
byte Minutes (0 to 59)
rd
th
3
& 4
bytes Milliseconds (0 to 59999)
Note: Clock resolution limited to 0.01 sec
Example: 1:15:48:572 stored as 17808828
st
(i.e., 1
word 010F, 2
F25
16 bits
UNSIGNED VALUE, 4 DECIMAL PLACES
Example: 0.1234 stored as 1234
F26
16 bits
UNSIGNED VALUE, 3 DECIMAL PLACES
6
Example: 1.234 stored as 1234
FC100
Unsigned
TEMPEATURE DISPLAY UNITS
16 bit integer
0 Celsius
1 Fahrenheit
FC101
Unsigned
RS 485 BAUD RATE
16 bit integer
0 300 baud
1 1200 baud
2 2400 baud
3 4800 baud
4 9600 baud
5 19200 baud
FC102
Unsigned
RS 485 PARITY
16 bit integer
0 None
1 Odd
2 Even
FC103
Unsigned
OFF / ON or NO/YES SELECTION
16 bit integer
0 Off / No
1 On / Yes
6-62
nd
word BDBC)
469 Motor Management Relay
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 4 of 14)
FORMAT
TYPE
DEFINITION
CODE
FC104
Unsigned
GROUND CT TYPE
16 bit integer
0 None
1 1 A Secondary
2 5 A Secondary
3 50/0.025 CT
FC105
Unsigned
DIFFERENTIAL CT TYPE
16 bit integer
0 None
1 1 A Secondary
2 5 A Secondary
FC106
Unsigned
VOLTAGE TRANSFORMER CONNECTION
16 bit integer
TYPE
0 None
1 Open Delta
2 Wye
FC107
Unsigned
NOMINAL FREQUENCY
16 bit integer
0 60 Hz
1 50 Hz
2 Variable
FC108
Unsigned
REDUCED VOLTAGE STARTING TRANSITION
16 bit integer
ON
0 Current Only
1 Current or Timer
2 Current and Timer
FC109
Unsigned
STARTER STATUS SWITCH
16 bit integer
0 Starter Aux a
1 Starter Aux b
FC110
Unsigned
ASSIGNABLE INPUT FUNCTION
16 bit integer
0 Off
1 Remote Alarm
2 Remote Trip
3 Speed Switch Trip
4 Load Shed Trip
5 Pressure Sw. Alarm
6 Pressure Switch Trip
7 Vibration Sw. Alarm
8 Vibration Sw. Trip
9 Digital Counter
10 Tachometer
11 General Sw. A
12 General Sw. B
13 General Sw. C