9.3.3 Inverter Register File Number Offset Format
The formula to calculate which register is targeted in the interface card is provided in Equation 3.
In Equation 3, "target register" ∈[1...1899], "file number" ∈[10...28] (which means N10...N28), and
"offset" is restricted only by the limitations of the programming software (but is a value of 1899 max).
Refer to section 4.1 for the register list. Table 35 provides some examples of various combinations of
file/section numbers and offsets/elements which can be used to access inverter registers. Note that
there are multiple different combinations of file/section numbers and offsets/elements that will result in
the same inverter register being accessed.
Table 34: CSP (PCCC) Read/Write Services
Service
PLC5 Typed Read
PLC5 Typed Write
PLC5 Word Range Read
PLC5 Word Range Write
SLC Typed Read
SLC Typed Write
(
target
register
file
number
=
PROTOCOL-SPECIFIC INFORMATION
Code
0x68
0x67
0x01
0x00
0xA2
0xAA
)
-
10
100
×
+
offset
Equation 3
9
163