PROTOCOL-SPECIFIC INFORMATION
Polarity
Indicates the relationship between the physical state of the object (as stored in the register) and the
logical state represented by the object's present value property. If the physical state is active high, select
"Normal" from this dropdown menu. If the physical state is active low, select "Reverse" from this
dropdown menu. For further detail, refer to the "Bitmask" behavioral description.
9.4.7.5

Binary Output Object Settings

Object Name
The name of the BACnet object. Enter a string of between 1 and 32 characters in length. All object
names must be unique within a node.
Instance
The BACnet object's instance number. Enter a value between 0...4194302 (0x0...0x3FFFFE).
Register
The inverter register number (refer to section 4) that the BACnet object's present value will access.
Bitmask
Specifies which bit(s) in the 16-bit value designated by the "Register" that the binary object will map to.
This mechanism allows up to 16 binary objects to be simultaneously assigned to one register (each
binary object mapping to a single bit of that 16-bit word). It is possible to map binary objects to multiple
9
bits within the designated register.